FY 2004 Energy Use and Recommended Energy Conservation Measures - Environmental Technology and National Security Buildings at Pacific Northwest National Laboratory

Abstract

This report addresses the question of why the ETB on PNNL's campus used about 20% more electricity than the NSB in FY 2004, even though ETB has more energy conservations installed than NSB and the two buildings were built using nearly identical floor plans. It was determined that the difference in electricity use between the two buildings was due to the large number of computers in the basement of ETB. It was further determined that ETB's high electricity consumption rate cannot be remedied until these computers can be relocated to a more suitable facility.

Revised: February 23, 2006 | Published: December 15, 2005

Citation

Olson N.J., D.L. Hadley, and R.M. Routh. 2005. FY 2004 Energy Use and Recommended Energy Conservation Measures - Environmental Technology and National Security Buildings at Pacific Northwest National Laboratory Richland, WA: Pacific Northwest National Laboratory.