July 16, 2010
Report

Assessment of the 3410 Building Filtered Exhaust Stack Sampling Probe Location

Abstract

Pacific Northwest National Laboratory performed several tests in the exhaust air discharge from the new 3410 Building Filtered Exhaust Stack to determine whether the air sampling probe for emissions monitoring for radionuclides is acceptable. The method followed involved adopting the results of a previously performed test series from a system with a similar configuration, followed by several tests on the actual system to verify the applicability of the previously performed tests. The qualification criteria for these types of stacks include metrics concerning 1) uniformity of air velocity, 2) sufficiently small flow angle with respect to the axis of the duct, 3) uniformity of tracer gas concentration, and 4) uniformity tracer particle concentration.

Revised: August 20, 2010 | Published: July 16, 2010

Citation

Glissmeyer J.A., and J.E. Flaherty. 2010. Assessment of the 3410 Building Filtered Exhaust Stack Sampling Probe Location Richland, WA: Pacific Northwest National Laboratory.