Rooftop package air-conditioning and heat pumps, while representing over half of U.S. commercial-building cooling energy consumption, are some of the most neglected of building systems. They are often found with inoperable dampers, dirty/clogged filters and coils, incorrect refrigerant charges, failing compressors, failed fans, missing enclosure panels, un-calibrated controls, failed sensors, and other problems. Frequently, actual operating hours deviate considerably from intended (and assumed) schedules. Although there are no reliable estimates on what fraction of the units operate under degraded conditions and the energy inefficiencies associated with such operations, a range of savings from 10 to 30% are generally believed to be achievable by enhancing operation of these units. Potential national energy savings from proper operation range from 23 to 70 trillion Btus annually in the U.S. Since the cost associated with conventional monitoring and servicing is quite high, conventional monitoring is seldom done. Combinations of wireless sensing and data acquisition, monitoring tools, automated diagnostics and prognostics show considerable promise to help remedy this maintenance problem for package HVAC units and the underserved small commercial building sector in which they are predominantly installed. This paper characterizes the current problem with maintenance of packaged air conditioners and heat pumps, provides estimates of the total energy impacts of the problem, and describes a generic system in which these developing technologies are used to provide real-time condition monitoring for package HVAC units and their components. Costs with today’s technology are provided and future costs are estimated, showing that benefits will greatly exceed costs in many cases particularly if low-cost wireless monitoring is used.
Revised: June 14, 2005 |
Published: June 1, 2004
Citation
Katipamula S., and M.R. Brambley. 2004.Wireless Condition Monitoring and Maintenance for Rooftop Packaged Heating, Ventilation, and Air-Conditioning. In 2004 Summer Study on Energy Efficiency in Buildings, 3-124 - 3-138. Washington, District Of Columbia:American Council for an Energy Efficient Economy.PNNL-SA-41084.