This paper presents simple and reliable method for predicting the islanding detection performance of vector surge relays. The relay performance is characterized by a tripping-time versus power-imbalance curve. With the curve, one can determine the time taken by a vector surge relay to detect islanding for any generation-load mismatch level. The main contribution of this paper is the development of analytical formulas for directly determining the behavior of vector surge relays. As a result, efforts needed to asses the relay performance for a given distributed generation scheme can be simplified significantly. The accuracy of the formulas has been verified by extensive simulation study results.
Revised: November 2, 2006 |
Published: January 1, 2005
Citation
Freitas W., Z. Huang, and W. Xu. 2005.A Practical Method for Assessing the Effectiveness of Vector Surge Relays for Distributed Generation Applications.IEEE Transactions on Power Delivery Vol 20.PNNL-SA-39501.