May 21, 2025
Conference Paper
Fault Contribution of Grid-Following and Grid-Forming Inverters Considering Generic Inverter Controls and Ride-through Requirements
Abstract
Gradual transformation of the synchronous generator (SG)-dominated power systems to inverter-based resource (IBR)-dominated power systems is bringing new challenges regarding power system protection. Increasing IBR’s penetration will reduce the reliability of protection coordination, originally developed for SG-dominated power systems, potentially leading to less accurate calculation or even mis-operation. Thus, new protection schemes compatible with IBR-dominated power systems should be established. Prior to establishing the protection schemes, research on the fault contribution of generic IBR models should be conducted considering interconnection requirements. This paper conducts fault current contribution analysis of generic grid-following (GFL) and grid-forming (GFM) inverters considering interconnection requirements using an electromagnetic transient (EMT) simulation tool. To do this, EMT-based generic GFL models have been developed with the ride-through requirements from IEEE-1547 standards. In addition, the major functions of the generic models are explained. Then, the fault current analysis was conducted using GFL and GFM inverters in a single-inverter-infinite-bus system and a modified IEEE 34-node system considering different grid, fault, inverter control parameters.Published: May 21, 2025